Water condensed modulating chillers with high performances MHW
|
|
|
![]() |
||
![]() |
Диапазон: 40 - 170 kW
Water condensed modulating chillers with high performances
Continuous capacity modulation
Max efficiency at partial loads
Extreme low-noise with Hi-Box®
Easy accessibility with Hi-Rail®
All compressors are installed in the brand new Hi-Box® for a very low noise emission and can be pulled out of the frame for easy maintenance thanks to the Hi-Rail® solution.
MHW is the last generation of water condensed chillers, designed with a combination of ON/OFF and BLDC inverter driven compressors.
Thanks to a dedicated control software, developed inside HiRef, MHW units provide a continuous modulation of the cooling capacity, don’t require buffer tanks and have reduced start-up currents.
The BLDC inverter driven compressors are frequency modulated in order to reach the highest cooling capacity or the highest energy efficiency in every single working point.
MHW can be connected to all Polymorph® by HiRef
MHW can be connected to all Polymorph® by HiRef for the highest flexibility of your systems.
- R410A refrigerant
- High specific capacity with a small footprint
- Quick water connections
- Easy spare parts availability thanks to shared components for the whole range
- AISI 316 stainless steel brazed plate heat exchangers
- Electronically controlled expansion valves
- Available in “cooling only” or “reversible heat pump” version
- Closed-frame execution available
Water Conditions: 20/15°C user side; 40/45°C + 34% e.g. source side
Maximum Capacity | Ед. изм. | 051 D | 061 D | 073 D | 083 D | 114 D | 124 D | 146 D | 166 D |
Cooling capacity | kW | 60 | 67 | 81 | 88 | 119 | 132 | 158 | 171 |
Compressors’ power input | kW | 16,1 | 19,4 | 20,3 | 24,2 | 31,6 | 38,4 | 42,3 | 47,5 |
EER | - | 3,75 | 3,44 | 3,96 | 3,63 | 3,75 | 3,43 | 3,73 | 3,61 |
Evaporator water pressure drops | kPa | 38 | 39 | 46 | 48 | 26 | 31 | 33 | 30 |
Condenser water pressure drops | kPa | 41 | 38 | 34 | 30 | 50 | 46 | 51 | 49 |
Maximum Efficiency | |||||||||
Cooling capacity | kW | 43 | 46 | 57 | 61 | 83 | 92 | 111 | 120 |
Compressors’ power input | kW | 10,4 | 11,1 | 13,5 | 14,4 | 20,1 | 22,0 | 27,1 | 29,1 |
EER | - | 4,12 | 4,19 | 4,21 | 4,24 | 4,13 | 4,17 | 4,10 | 4,11 |
Evaporator pressure drops | kPa | 19 | 19 | 23 | 23 | 13 | 15 | 16 | 15 |
Condenser pressure drops | kPa | 20 | 17 | 16 | 14 | 23 | 20 | 24 | 23 |
FLA ( full load amperage ) | A | 37 | 42 | 49 | 54 | 74 | 84 | 98 | 108 |
Number of compressors | - | 2 | 2 | 3 | 3 | 4 | 4 | 6 | 6 |
Refrigerating circuits | - | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 |